118
118 EN
MANUAL ELDES ESIM264 V3.1
2. Disconnect alarm system ESIM264 power supply and backup battery before connecting the wires.
Z2 Z1
COM Y
G
AUX-
AUX+
EKB3
ESIM264
Y
G
AUX- AUX+
5,6kΩ
46
3. Wire up keypad terminals to ESIM264 alarm system respectively – AUX+ to AUX+, AUX- to AUX-, Y to Y, G to G. (see Fig. No. 46).
4. Connect a sensor and the resistor across Z1 and COM terminalss in accordance with zone connection Type 1 or Type 2 (see 2.3.2. Zone
Connection Types). As keypad zone Z1 is disabled by default, it can be enabled by SMS, ELDES Conguration Tool, EKB2 and EKB3 key-
pad. Z2 terminal is permanently inactive. Keypad zone Z1 must be enabled and resistor connected even if the tamper button alone is
required (see Fig. No. 44).
NOTE: Keypad zone connection type can dier from selected on-board zone connection type.
NOTE: ATZ mode is NOT supported by keypad zones. ATZ mode is ineective for keypad zones when enabled.
5. Set the keypad address by combining DIP switch positions (see 31.1.2.1.5 Keypad Address).
6. Inx the keypad into the holder (see Fig. No. 45).
ATTENTION: Before xing the keypad into the holder please , make sure that the tamper is properly pressed (see Fig. No. 44).
7. Power up ESIM264 alarm system.
8. EKB3 keypad is ready.
For more details on multiple keypad wiring, please refer to 3.2.7. RS485.
31.1.2.3. Visual and Audio Indications
EKB3 keys have a LED back-light, therefore it is possible to use this keypad even in dark premises. The back-light lasts for 3 minutes after the
last key-stroke while the system is disarmed. In case of alarm, the keypad back-light turns ON and lasts until the system is disarmed.
The built-in buzzer uses two types of sound signals – three short beeps and one long beep. Three short beeps stand for successfully carried
out conguration command, one long beep – for invalid conguration command. In addition, the buzzer emits short beeps in case of alarm and
exit/entry delay countdown.
31.1.2.4. EKB3 Zone & Tamper
Keypad EKB3 has one wired zone Z1 and one tamper button. By default, the keypad zone Z1 is disabled. The keypad zone can be enabled by
SMS, EKB2 keypad, EKB3 keypad, EKB3W keypad and ELDES Conguration Tool software (see 14.9. Disabling and Enabling Zones). Zone
Z1 is enabled, it operates like any other system zone, therefore a sensor can be connected to it. In addition, Z1 and COM terminals must be
connected with resistor of 5,6k nominal.
The tamper button is intended for monitoring the enclosure status of EKB3, therefore the system causes alarm if the enclosure is illegally
opened. Keypad zone Z1 must be enabled and resistor connected even if the tamper button alone is required.
Comments to this Manuals