2.3. Wiring Diagrams
2.3.1. General Wiring
C O M
BELL-
BELL+
G
Y
C2
AUX-
AUX+
AC /DC
AC /DC
Z1
C O M
Z2
Z3
C O M
Z4
DATA
+5V
MIC -
MIC +
BUZ-
C1
BUZ+
C O M
C O M
Z6
Z5
MIC
BUZ
SIREN/BELL
iButton®
key reader
Temperature sensor
EKB2EKB3
EPGM1
Z1
Z2
Backup Battery
12V 1.3-7Ah
Metal cabinet
PE terminal
Relay
module
500mA max.
Z4
Z3
Z5
Z6
Fuse 500 mA
~230V 50Hz
~16-24V
AKU+
AKU-
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
5,6 kΩ
2
2.3.2. Zone Connection Types
Type 1 Example of 4-wire smoke detector wiring
Z1
COM
AUX+
+Vin
GND
C1
COM
NO
5,6 kΩ
3
6-Zone mode: Nor-
mally open contact
with 5,6K end-of-
line resistor.
Type 2 Example of magnetic door contact wiring
6-Zone mode: Nor-
mally closed contact
with 5,6K end-of-
line resistor
COM
NC
Magnet
COM
Z1
5,6 kΩ
4
NOTE: Based on the example given, in the event of an alarm, the smoke detector could be reset by turining OFF and ON the PGM
output C1. For more details, please refer to 18.4. Turning PGM Outputs ON and OFF.
NOTE: The system does NOT support 2-wire smoke detectors.